Toshiba H9 Manuel d'utilisateur Page 47

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 289
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 46
H9 ASD Installation and Operation Manual 39
Command Control Selections
The following is a listing with descriptions of the
Command Mode (
F003) selections (Program
Fundamental Standard Mode Selection Command
Mode Selection)
.
Settings:
0 — Terminal Block
Allows for Command control input via the
Terminal Board.
2 — EOI Keypad
This setting is used for EOI command control.
3 — RS485 (4-wire)
Use this setting if using a remotely-mounted EOI for command control. Connect the EOI to the
RJ45 connector of the Terminal Board.
4 — Communication Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode (
F004) selections (Program
Fundamental Standard Mode Selection
Frequency Mode 1).
Settings:
1 — V/I
This selection is used when a 0 to 10-volt DC
analog input or a 0 – 20 mA DC current input
is used as the speed control input. Only one input signal type may be used at a time. Set SW301
to the desired signal type.
2 — RR
This selection is used for a 0 to 10-volt DC analog input signal.
3 — RX
This selection is used for a -10 to +10-volt DC analog input signal.
5 — EOI Keypad
This setting is used for EOI frequency control.
6 — RS485 (4-wire)
Use this setting if using a remotely-mounted EOI for frequency control. Connect the EOI to the
RJ45 connector of the Terminal Board.
7 — Communication Option Board
Use this setting if using the optional Communication Board for frequency control.
8 — RX2 Option (AI1)
This selection is used for a -10 to +10-volt DC analog input signal.
(Default)
(Default)
Vue de la page 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 288 289

Commentaires sur ces manuels

Pas de commentaire