G8000 Series Installation and Operation Manual
G8000 Series Installation Manual
26
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
4 of 16mm-diameter
(5/8”) screw holes
Anchor Bolt
4 screw holes
(Side View)
Front
Back
551mm
(21” 11/16)
1,170mm (46” 1/16)
< 100kVA (T80S3K10KK6XSNH) >
< 150/225kV
A
>
4 x 12mm-Dia.
(
1/2”
)
551mm
(21” 11/16)
754mm (29” 11/16)
< 100kVA (T80S3K10KK6XS2H) >
Front
Back
4 x 12mm-Dia.
(
1/2”
)
572mm
(22” 1/2)
572mm
(22” 1/2)
572mm
(22” 1/2)
650mm
(25” 19/32)
< 250/300kVA >
8 x 12mm-Dia.
1/2”
Front
Back
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the oor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specied UPS models.
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS