7.2 System Parameters Adjustment Range and Factory Settings (cont'd)
PARAMETER
DISPLAY
ITEM
NO.
PARAMETER
DESCRIPTION
ADJUSTMENT
RANGE
FACTORY
SETTING
REFERENCE
PAGE
• 1 n r
. LI • ' 1 l-l
JUMP FREQUENCY GROUP PARAMETERS **
• r II
, I LI 1
1 Jump frequency #1 0.0 Hz - FH 0.0 Hz 9-7
• I r II
• LI 1 LI '
2 Jump width #1 0.0 Hz - FH 0.0 Hz 9-7
• r 11
• ' LI L
3 Jump frequency #2 0.0 Hz - FH 0.0 Hz 9-7
• I r 1 “1
• LI 1 U L
4 Jump width #2 0.0 Hz - FH 0.0 Hz 9-7
• r 1 J
, r LI
5 Jump frequency #3 0.0 Hz - FH 0.0 Hz 9-7
• ( r 11
, LI 1 LI J
6 Jump width #3 0.0 Hz - FH 0.0 Hz 9-7
• L L M 1
.1 LI. r 1
7 PID setpoint control select 0: Off
1: On
0 9-7
• (1
• LI 1
8 Proportional gain 0 - 9999 1000 9-7
• r 1
• LI >
9 Integral gain 0 - 9999 500 9-7
• (1
• LI M
10 Differential gain 0 - 255 0 9-7
• r r r
• LI 1 J
11 Lag time constant 0 - 255 255 9-7
• 1 (1
.(-/.( 1 LI
DISPLAY GROUP PARAMETERS **
• J r n 1
. LI J 1 . L
1 Universal unit multiplication factor 0.00 - 200.0
(0.00 = OFF)
0.00 9-8
• 1 r
• L r
2 Low speed detection 0.0 Hz - FH 0.5 Hz 9-8
• r 1 I
,1 L M
3 Speed reach selection 0: Complete ACC/DEC
1: Frequency reach
reference
1 9-8
• r M
.1 1 L M 4 Speed reach detection range 0.0 Hz - FH 2.5 Hz 9-8
• r r 1 1
• 1 / L M
5 Speed reach reference 0.0 Hz - FH 60.0 Hz 9-8
• 1 1 r
• LI LI I
6 DC injection voltage start frequency 0.0 Hz - 10.0 Hz 0.0 Hz 9-8
• 11/
, LI LI L
7 DC injection voltage 0 - 20 % 0 % 9-8
• III
, LI IJ L
8 DC injection time 0.0 - 5.0 sec 0.0 sec 9-8
• ll nil /
• r.lj LI L
9 Output voltage regulation 0 - 100 % 100 % 9-8
• ll n (“ /“
• Ll 1 J, J
10 Overvoltage stall protection select 0: On
1: Off
0 9-8
• r ri /“
.1.1 1 Ll
SPEED GROUP PARAMETERS **
• r r 1 1 r
. L , L II IJ
1 AC line/inverter transfer signal 0: Off
1: On
0 9-9
• r 1
.-If I
2 Multispeed run frequency #1 LL - UL 0.0 Hz 9-9
• r 1
. -1 I L
3 Multispeed run frequency #2 LL - UL 0.0 Hz 9-9
• L _ 1
. -1 ' 1
4 Multispeed run frequency #3 LL - UL 0.0 Hz 9-9
• r II
.-If 1
5 Multispeed run frequency #4 LL - UL 0.0 Hz 9-9
• r r
.-If -f
6 Multispeed run frequency #5 LL - UL 0.0 Hz 9-9
• r r
. -1 1 Ll
7 Multispeed run frequency #6 LL - UL 0.0 Hz 9-9
• r r r
. 1 -f Ll 1
8 Firespeed override frequency (Sr7) LL - UL 0.0 Hz 9-9
7-4