2.2 Wiring
When conducting wiring, follow the instructions below.
• Use shield wire for control signal line and ground the unit with shield wire
.
(Use twisted pair shield cable for wiring of the analog monitor output.
)
• Applicable wire size ...................................... TB1: 0.2 to 2.5 mm
2
TB2, TB3: 0.2 to 1.5mm
2
• The wire length of peel off the end ............... TB1: About 5mm
TB2, TB3: About 7mm
• Using screwdriver .........................................TB1: The blade tip has 0.6mm thickness
and 3.5mm width.
TB2, TB3: The blade tip has 0.4mm thickness
and 2.5mm width.
• Tightening torque of the terminal block ........ TB1: 0.5 to 0.6 N
・m
TB2, TB3: 0.22 to 0.25 N
・m
• Never bind the signal line and main circuit connection wire together
.