Vue de la page 43
43
11.2.7
11.2.711.2.7
11.2.7
GROUP:PROTECTION FUNCTION PARAMETERS
GROUP:PROTECTION FUNCTION PARAMETERSGROUP:PROTECTION FUNCTION PARAMETERS
GROUP:PROTECTION FUNCTION PARAMETERS
Register Function / Title Bank Mask Adjustment Range Multiplier
11F
DYNAMIC BRAKING
SELECTION
0 / 1 0003 0000: no dynamic braking (0)
0001: with dynamic braking, no DBR
overload trip (1)
0003: with dynamic braking and
DBR overload trip (2)
120 2
BRAKING RESISTOR
VALUE
0 / 1 FFFF
000A 2710 (1.0 1000)
0.1
121
BRAKING RESISTOR
POWER RATING
0 / 1 FFFF
0001 EA60 (0.01 600.00)
0.01
122
OVERVOLTAGE STALL
PROTECTION
0 / 1 0004 0000: ON (0)
0004: OFF (1)
123
DC INJECTION START
FREQUENCY
0 / 1 FFFF
0000 2EE0 (0.00 120.00)
0.01
124 Other
than 0
DC INJECTION
CURRENT
MAGNITUDE
0 / 1 00FF
0000 0064 (0 100)
1
125
DC INJECTION
TIME
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
126
FWD/REV DC INJECTION
PRIORITY CTRL
0 / 1 0040 0000: OFF (0)
0040: ON (1)
127
MOTOR SHAFT
STATIONARY CTRL
0 / 1 0080 0000: OFF (0)
0080: ON (1)
128
EMERGENCY OFF MODE
SELECTION
0 / 1 0030 0000: Coast stop (0)
0010: Decelerated stop (1)
0020: DC injection stop (2)
129 2
EMERGENCY OFF DC
INJECTION TIME
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
12A
NUMBER OF RETRY
ATTEMPTS
0 / 1 00FF
0000 000A (0 10)
1
12B Other
than 0
TIME BETWEEN
RETRY ATTEMPTS
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
12C
REGENERATION POWER
RIDE-THROUGH
0 / 1 0008 0000: OFF (0)
0008: ON (1)
12D 1
REGENERATION
RIDE-THROUGH TIME
0 / 1 00FF
0000 00FA (0.0 25.0)
0.1
12E
AUTO-RESTART (MOTOR
SPEED SEARCH)
0 / 1 0018 0000: OFF (0)
0008: On power failure (1)
0010: On ST make/break (2)
0018: Both (1) and (2) (3)
12F
ELECTRONIC THERMAL
PROTECT LVL #1
0 / 1 00FF
000A 0064 (10 100)
1
130
OVERLOAD REDUCTION
START FREQ
0 / 1 FFFF
0000 0BB8 (0.00 30.00)
0.01
131
MOTOR 150% OVERLOAD
TIME LIMIT
0 / 1 00FF
0001 00F0 (10 2400)
10
132
OVERLOAD SELECTION
0 / 1 0030 0000: with motor overload trip,
without soft-stall (0)
0010: with motor overload trip and
soft-stall (1)
0020: without soft-stall or motor
overload trip (2)
0030: with soft-stall, without motor
overload trip (3)
133
STALL PROTECTION
ENABLE
0 / 1 0040 0000: ON (0)
0040: OFF (1)
134 0
STALL PROTECTION
CURRENT LEVEL
0 / 1 00FF
000A 00D7 (10 215)
1