G9000 Installation and Operation Manual 23
Batt. Capacity Required
at Full Load Output
±1% (0 – 100% balanced load); ±2% (0 – 100% unbalanced load)
± 5.0% (in 0.5 V increments)
2% maximum at 100% unbalanced load
< 2% THD at 100% linear load; < 5% THD at 100% nonlinear load
±2% maximum at 100% load step; ±1% maximum at loss/return of AC power;
±5% maximum at load transfer to/from static bypass
±1% to ± 5% (selectable in 1% increments)
1 Hz/s to 5 Hz/s (selectable in 1 Hz/s increments)
±0.01% in free running mode
±1 @ 100% Balanced Load, ±3 @ 100% Unbalanced Load
0.9 (0.9 Lagging to 0.95 Leading within output kW rating)
125% for 2 minutes; 150% for 60 seconds
125% for 10 minutes; 150% for 60 seconds
65,000 A (with optional fuses)
100,000 A (with optional fuses)
32 F to 104 F (0 C to 40 C). Recommended : 68゚F to 86゚F ( 20 C to 30 C)
0 to 7380 feet No Derating at 40゚C
Indoor (free from corrosive gases and dust)
Top: 20 in. (508 mm)
Front: 40 in. (1016 mm)
Rear: 0 in. (0 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no sidecars used.
Top: 23.6 in. (600 mm)
Front: 42.3 in. (1075 mm)
Rear: 0 in. (0 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if
no sidecars used.