5.8 Terminal Connections and Functions (cont'd)
TOSHIBA
Terminal
name
Terminal functions Terminal
location
ST
CC
(one of three)
SSI
JOG(SS2)
AD2(SS3)
RST
CC
(one of three)
Input terminal for run interlock. When ST is shorted to CC, the inverter
is ready to run. With ST-CC open the unit will not run and if opened
while running a coasting stop begins.
Input terminal for forward run. When F is shorted to CC, a forward
run starts. With F-CC open, the unit decelerates to a complete stop.
Input terminal for reverse run. When R is shorted to CC, a reverse run
starts. With R-CC open, the unit decelerates to a complete stop.
If terminals F-CC and R-CC are shorted simultaneously, a reverse
run occurs.
This is the common return for ST terminal.
Do not connect to GND(E).
Input terminal for multi-speed run frequencies. Depends on setting of
function [1 .tb], JOG/SS2 and AD2/SS3 terminals. (See Page 10-1)
Input terminal for jogging run or multi-speed run frequencies. Depends
on setting of function [l.tb], SSI, AD2(SS3) terminals. (See Page 10-1)
Input terminal for multispeed run frequencies. Depends on setting of
function [l.tb], SSI, JOG/SS2 terminals. (See Page 10-1)
With RST-CC shorted, the inverter's protective function resets.
This is the common return for ST, F, R, SSI, JOG(SS2), AD2(SS3),
and RST terminals. S
o not connect to GND(E).
Control
PWB
terminal
block
GND(E)
(three provided)
The inverter earth ground terminal.
Do not connect to common return terminal (CC).
Frame
screw or
lug
R41/46
R40/44 *
R38
RJ *
R20/22
R10/11 *
T10/11 T20/22
Jumper to RJ when using 415V-50Hz/460V-60Hz incoming power.
Do not jumper to R40/44 or R38.
Jumper to RJ when using 400V-50Hz/440V-60Hz incoming power.
Do not jumper to R41/46 or R38.
Jumper to RJ when using 380V-50Hz incoming power.
Do not jumper to R41/46 or R40/44.
Common for input power selection. Jumper to either R41/46, R40/44,
or R38. Do not jumper to more than one terminal at a time.
Output power terminal. Supplies 1-phase 200V-50Hz or 1-phase
220V-60HZ @ 40VA maximum.
Output power terminal. Supplies 1-phase 100V-50Hz or 1-phase
110V-60HZ @ 40VA maximum.
Output power return terminal for either 1-phase 200V-50Hz/220V-60Hz
@ 40VA or 1-phase 100V-50Hz/110V-60Hz @ 40VA.
Terminal
block
A
Supplied only on the Q2-4055 through Q2-420K units.
5-8