E6581741h
TOSVERT VF-MB1/S15
EtherNet/IP™ - Modbus
®
TCP option
Function Manual
IPE002Z
NOTICE
1. Read this manual before installing or operating. Keep this instruction manual on hand
of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
Vue de la page 0
1 2 3 4 5 6 ... 88 89

Résumé du contenu

Page 1 - E6581741h

E6581741h TOSVERT VF-MB1/S15 EtherNet/IP™ - Modbus® TCP option Function Manual IPE002Z NOTICE 1. Read th

Page 2 - Caution

E6581741 - 9 - Title Communication No. Function Description Factory settingc500 C500 Protocol (*3) This parameter is used to set the protocol of th

Page 3 - Table of Contents

E6581741 - 10 - EtherNet/IP parameters Title Communication No. Function Description Factory settingc536 C536 EtherNet Error Monitor of the EtherNet

Page 4

E6581741 - 11 - 3.2. The details of the parameter setting 3.2.1. Device name (c081-c096) This option module can set the "Device name" o

Page 5 - 2. Names and functions

E6581741 - 12 - 3.2.2. Assigning IP addresses (c504, c505-c516) The drive needs 3 (4-Modbus TCP) IP addresses. *The drive IP address. *The subnet m

Page 6

E6581741 - 13 - 3.2.3. Network error detection (c100 - c103, c523) ▼Display of trip information err8 (Optional unit fault 1: 1BH): Network error st

Page 7 - 2.4. LED indicator

E6581741 - 14 - 3.2.4. Command data (c001-c006), Monitor data (c021-c026) The outline is indicated about the setting item of parameter c001 – c006 a

Page 8 - 3. Parameters

E6581741 - 15 - 3.2.4.2. fa06 (Communication command1) bit Function 0 1 Note 0 Preset speed operation frequencies 1 1 Preset speed operation fr

Page 9

E6581741 - 16 - 3.2.4.3. fa23 (Communication command 2) bit Function 0 1 Note 0 (Reserved) - - - 1 Electric power quantity reset OFF Reset E

Page 10 - E6581741

E6581741 - 17 - 3.2.4.4. fa07 (frequency reference from internal option) Frequency reference is set up by 0.01Hz unit and the hexadecimal number.

Page 11 - Warning

E6581741 - 18 - 3.2.4.7. fd01 (Inverter operating status 1) bit Function 0 1 Note 0 Failure FL No output Under in progress - 1 Failure Not t

Page 12

E6581741 - 1 - - 1 -Introduction Thank you for purchasing the “EtherNet/IP™ - Modbus® TCP option (IPE002Z)” for TOSVERT VF-MB1/S15 inverter. Before

Page 13

E6581741 - 19 - 3.2.4.9. fd03 (Output current) The output current is read into 0.01% of units and by the hexadecimal number. For example, when t

Page 14

E6581741 - 20 - 3.2.4.13. fc91 (Alarm code) bit Function 0 1 Remarks (Code displayed on the panel) 0 Over-current alarm Normal Alarming c flickin

Page 15

E6581741 - 21 - 3.2.4.15. fd07 (Output TB Status) bit TB Name Function (Parameter) 0 1 0 RY-RC Output terminal function selection 1A (f130

Page 16

E6581741 - 22 - 4. Objects This section contains the object specifications for all EtherNet/IP objects currently supported by the “IPE002Z”. Table 1

Page 17

E6581741 - 23 - 4.1. Identity Object (0x01) Class code 0x01. This object provides identification of and general information about the device. C

Page 18

E6581741 - 24 - Attribute 5 State Descriptions Adapted from document [CIP] “THE CIP NETWORKS LIBRARY” Bit Called Definition 0 Owned TRUE indicat

Page 19

E6581741 - 25 - 4.2. Message Router Object (0x02) Class code 0x02. The Message Router Object provides a messaging connection point through which

Page 20

E6581741 - 26 - 4.3. Assembly Object (0x04) Class code 0x04. The Assembly Object binds attributes of multiple objects, which allows data to or fr

Page 21

E6581741 - 27 - 4.4. Connection Manager Object (0x06) Class code 0x06. Use this object for connection and connectionless communications, includ

Page 22

E6581741 - 28 - 4.5. Motor Data Object (0x28) Class code 0x28. This object serves as a database for motor parameters. Class Attributes Instance

Page 23 - 4. Objects

E6581741 - 2 - Table of Contents 1. OVERVIEW ...

Page 24 - 4.1. Identity Object (0x01)

E6581741 - 29 - 4.6. Control Supervisor Object (0x29) Class code 0x29. This object models all the management functions for devices within the “Hi

Page 25

E6581741 - 30 - Instance Services Service Code Service Name Description of Service 0x05 Reset Resets the drive to the start-up state. 0x0E G

Page 26

E6581741 - 31 - 4.6.1. Run/Stop Event Matrix Run1 Run2 Trigger Event Run Type 0 0 Stop No Action 0 -> 1 0 Run Run1 0 0 -> 1 Run Ru

Page 27 - 4.3. Assembly Object (0x04)

E6581741 - 32 - 4.7. AC/DC Drive Object (0x2A) Class code 0x2A. This object models the functions specific to an AC or DC Drive. e.g. speed ramp,

Page 28

E6581741 - 33 - 4.8. Parameter Objects (0x64) Class code 0x64. This object provides VF-MB1/ S15’s Parameter access. Range Address accessed: Input

Page 29

E6581741 - 34 - Instance Services Service Code Service Name Description of Service 0x0E Get_Attribute_Single Read one attribute 0x10 Set_Attribu

Page 30

E6581741 - 35 - 4.9. Parameter Objects (0x65) Class code 0x65. This object provides VF-MB1/S15’s Parameter access. Range Address accessed: Input In

Page 31

E6581741 - 36 - 4.10. Port Object (0xF4) Class code 0xF4. The Port Object enumerates the CIP ports present on the device. One instance exists for

Page 32 - 4.6.2. State of the drive

E6581741 - 37 - 4.11. TCP/IP interface Object (0xF5) Class code 0xF5. The TCP/IP Interface Object provides the mechanism to configure a device’s TCP

Page 33

E6581741 - 38 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Status DWORD Bits 0 -3 : Interface configurat

Page 34

E6581741 - 3 - 8.7. "23 (0x17) Read/Write Multiple Registers" function...

Page 35

E6581741 - 39 - Instance Attribute ID Access Name Data type Details Mcast Config STRUCT of IP Multicast address configuration Alloc Config US

Page 36

E6581741 - 40 - 4.12. Ethernet link object (0xF6) Class code 0xF6: The Ethernet Link Object maintains link-specific counters and status information

Page 37 - 4.10. Port Object (0xF4)

E6581741 - 41 - Instance 1 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Page 38

E6581741 - 42 - Instance Attribute ID Access Name Data type Details Media Counters STRUCT of Media-specific counters Alignment Errors UDINT

Page 39

E6581741 - 43 - Instance 2 Attribute Instance Attribute ID Access Name Data type Details 1 Get Interface Speed UDINT Interface speed currently

Page 40

E6581741 - 44 - 5. Configuration of the assemblies 5.1. List of Assembly Object Instance Output Instance Instance name Number (Hex) Size CIP ba

Page 41

E6581741 - 45 - 5.1.1. Instance 20: CIP basic speed control output Instance 20 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0

Page 42

E6581741 - 46 - 5.1.3. Instance 21: CIP extended speed control output Instance 21 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Page 43

E6581741 - 47 - 5.1.5. Instance 100: Native drive output Instance 100 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 DC brakin

Page 44

E6581741 - 48 - Examples of Instance 100/150 ① Stop Instance Byte 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex. 1, 0 0 0 00000000000 0 0 0 0x

Page 45 - Input Instance

E6581741 - 4 - 1. Overview The EtherNet/IP™ - Modbus® TCP option (IPE002Z) allows the VF-MB1/S15 inverter to be connected into the EtherNet/IP™ - Mo

Page 46

E6581741 - 49 - 5.1.7. Instance 101: Native drive output Instance 101 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 - Net Ref

Page 47

E6581741 - 50 - Examples of Instance 101/151 Access the inverter parameter is enabled using byte 4 to 6 of this Instance. Set the communication nu

Page 48

E6581741 - 51 - 5.1.9. Instance 102: Native drive output Instance 102 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 c001 Com

Page 49

E6581741 - 52 - 5.1.11. Instance 105: TOSHIBA specific output Instance 105 mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 1 F

Page 50

E6581741 - 53 - Examples of Instance 105/155 Access the inverter parameter is enabled using byte 1 to 5 of this Instance. Set the communication nu

Page 51

E6581741 - 54 - 6. About EDS file As for acquisition of an EDS file for VF-MB1 and VF-S15, please contact your Toshiba distributor. 7. Integratio

Page 52

E6581741 - 55 - 7.2. Add a EtherNet/IP scanner to the I/O configuration Right-click the I/O Configuration, and select “New Module”.

Page 53

E6581741 - 56 - Select the Module as below. Select revision of drive. Put in Name and IP address, and press “OK” button.

Page 54

E6581741 - 57 - 7.3. Configure the VF-MB1/S15 EtherNet/IP module Right-click the EtherNet/IP scanner, and select “New Module”.

Page 55 - 7. Integration in RSLogix™

E6581741 - 58 - Above the Allen-Bradley drive profile is selected. Select the format of the data. Above the CIP basic speed control

Page 56

E6581741 - 5 - 2.2. RJ45 connector pin layout The EtherNet/IP™ - Modbus® TCP option is equipped with two shielded RJ45 connectors. When you use VF

Page 57

E6581741 - 59 - 7.4. Download the program to the PLC The first download follows the following procedure. Select the using

Page 58

E6581741 - 60 - Select the "Download." Once again, select the "Download."

Page 59

E6581741 - 61 - 7.5. Edit the I/O scan data Open the "Controller Tags." Set to the "Offline" if change the

Page 60

E6581741 - 62 - Download the changed data to the PLC. : "Communications" J "Download" After the setting i

Page 61

E6581741 - 63 -

Page 62 - 7.5. Edit the I/O scan data

E6581741 - 64 - 8. Modbus TCP server 8.1. Modbus TCP frames Modbus TCP frames consist of a header and a Modbus request. Header format: Byte Descr

Page 63

E6581741 - 65 - 8.4. "03 (0x03) Read Holding Registers" function The Modbus request is used to read the values of a number (No. of Points

Page 64

E6581741 - 66 - 8.5. "06 (0x06) Write Single Register" function This Modbus request is used to write a given value (Present Data) to the

Page 65 - 8. Modbus TCP server

E6581741 - 67 - 8.6. "16 (0x10) Write Multiple Registers" function This Modbus request is used to write a number (No. of Registers) of ad

Page 66

E6581741 - 68 - 8.7. "23 (0x17) Read/Write Multiple Registers" function The "Read/Write Multiple Registers" service is reserved

Page 67

E6581741 - 6 - 2.4. LED indicator The LED shows the present status of the network and module. The behavior of LNK LED Link Activity Protocol

Page 68

E6581741 - 69 - 8.8. "43 (0x2B) Read Device identification" function The "Read/Write Multiple Registers" service is reserved fo

Page 69

E6581741 - 70 - Response format: (ID = 251) Byte Meaning With the IPE002Z 0 Function Code = 2Bh 2Bh 1 Type of MEI 0Eh 2 Read Device ID code

Page 70

E6581741 - 71 - 8.9. Parameter data It is explanation by the reference method of the list of parameters of the VF-MB1 or VF-S15 series as follows. F

Page 71

E6581741 - 72 - 9. IO Scanning service 9.1. Presentation The IO Scanning service is used to exchange I/O data between:  A controller or PLC (IO Sc

Page 72 - 8.9. Parameter data

E6581741 - 73 - 10. Example of the setup with PL7™ It is an example of the setup using PLC (PL7™) made by Schneider electric as follows. 10.1. Def

Page 73 - 9. IO Scanning service

E6581741 - 74 - 10.2. BOOTP configuration The BOOTP server function consists of allocating BOOTP clients their IP addresses. The activation conditio

Page 74

E6581741 - 75 - 10.3. Configuring Modbus messaging To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway address” parameters

Page 75 - 10.2. BOOTP configuration

E6581741 - 76 - 10.4. Configuring periodic variables This window is used to configure the IO Scanning function, described in the IO Scanning Service

Page 76

E6581741 - 77 - 11. Command & Setpoint selection (Local/Remote) Indication to display Local/Remote mode is on the inverter unit (Refer to the i

Page 77

E6581741 - 78 - <Example of setting> The example below shows how to configure the local/remote operation. F terminal ... Operatin

Page 78

E6581741 - 7 - 3. Parameters 3.1. Communication parameters Set up the inverter parameters as follows. It is necessary to reset the inverter to upd

Page 79 - EtherNet/IP-Modbus TCP

E6581741 - 79 - 12. Unusual diagnosis 12.1. Option error An error message is displayed when the hardware error or software error or lose of connect

Page 80 - 12. Unusual diagnosis

E6581741 - 80 - 13. WebServer The option has webserver function. Writing and reading the drive's parameter and the communication can be monito

Page 81 - 13. WebServer

E6581741 - 81 - From the TOSVERT home page, you can access to 3 main menus:  Monitoring  Network setup  Diagnostics 13.2. Web

Page 82 - 13.2. Web pages structure

E6581741 - 82 - 13.3. Drive monitor (Main menu: Monitoring) The state of the drive can be confirmed on this page.

Page 83

E6581741 - 83 - 13.4. Drive parameters (Main menu: Monitoring) The parameters of the drive can be set on this page. The left column is used to selec

Page 84

E6581741 - 84 - Input the write value to popup window.

Page 85

E6581741 - 85 - 13.5. Network parameters (Main menu: Network Setup) The network parameters of the drive can be confirmed on this page.

Page 86

E6581741 - 86 - 13.7. EthIP scanner (Main menu: Network Setup) The I/O scanner of the EtherNet/IP protocol can be set on this page.

Page 87

E6581741 - 87 - 13.8. Administration (Main menu: Network Setup) The "web read password" and "web write password" of the webserve

Page 88

E6581741 - 88 - 13.9. TCP/IP statistics (Main menu: Diagnostics) You can check TCP/IP status on this page. - 88E-

Page 89

E6581741 - 8 - Title Communication No. Function Description Factory settingc021 C021 Scanner output 1 address (*3)0: - 1: fd01 (Status informatio