2. Specification
32-point AC output
(cont'd)
Terminal connections
Load power supply
100to240Vdc
NOTE Minimum 24 Vac can be used as the load voltage.
However, if ioad voltage becomes 85 Vac or less, the
fusing detection circuit may work, in this case, aithough
AC output operation has no problem, the fusing display
LED (FL, FH) will light.
User's manual - Hardware 43