13.6.2 Supported Subpoints
This application contains a predefined set of FLN subpoints (refer to Table 4).
These points are static for this application, and cannot be edited.
Table 4: Supported Subpoints
Point
#
Point
Type
Subpoint
Name
Factory
Default
Units Slope Intercept
On
Text
Off
Text
01 LAO ADDRESS 99 1 0
02 LAO APPLICATION 2750 1 0
03 LAI FREQ OUTPUT 0 HZ 0.01 0
04 LAI OUTPUT CUR 0 A 0.01 0
05 LAI OUTPUT VOLT 0 V 0.1 0
06 LAI SPECIAL MON 0 - 1 0
07 LAO MON SELECT 0 - 1 0
08 LAO ACCEL TIME 50 SEC 0.1 0
09 LAO DECEL TIME 100 SEC 0.1 0
10 LDO CMD FWD.STOP STOP – 1 0 FWD STOP
11 LDO CMD REV.STOP STOP – 1 0 REV STOP
12 LAO FREQ CMD 0 HZ 0.01 0
13 LAO MIN FREQ 0 HZ 0.01 0 - -
14 LAO FREQ JUMP A 32767 HZ 0.01 0 - -
15 LAO FREQ JUMP B 32767 HZ 0.01 0 - -
16 LDI ALARM OUTPUT 0 1 0 ALARM -
17 LDI RUNNING STOP – 1 0 RUN STOP
18 LAO PID SET PNT 0 PCT 0.01 0 - -
19 LDO RESET CMD 0 1 0 RESET -
20 LAO OVRD TIME 1 HRS 1 0
21 LDI ASD COMM NO - 1 0 YES NO
22 LAO OPER MODE 0 - 1 0 - -
29 LDO DAY.NIGHT DAY 1 0 NIGHT DAY
99 LAO ERROR STATUS 0 1 0
Notes:
Points not listed are not used in this application.
All points have the same value for English units and SI units.