6.6 Operation frequency
6.6.1 Starting frequency
H : Starting frequency setting
Function
The frequency set with
H is put out as soon as operation is started.
Use the
H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Adjustment range Default setting
H Starting frequency setting 0.5-10.0 (Hz) 0.5
6.6.2 Run/stop control with frequency setting signals
H : Operation starting frequency
H
: Operation starting frequency hysteresis
Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting
H Operation starting frequency 0.0-HJ (Hz) 0.0
H Operation starting frequency hysteresis 0.0-HJ (Hz) 0.0
0A B 100%
Frequency command value
H
+
H
H
H
-
H
HJ
The inverter begins accelerating after
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.
Output frequency [Hz]