Toshiba VF-FS1 Manuel d'utilisateur Page 83

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 252
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 82
E6581381
E-17
5
[Parameter setting]
Title Function Adjustment range Default setting
WN
Upper limit frequency 0.5 - HJ (Hz)
50.0 (WP type)
60.0 (WN type)
NN
Lower limit frequency 0.0 - WN (Hz) 0.0
5.9 Base frequency
XN : Base frequency 1
XNX : Base frequency voltage 1
Function
Sets the base frequency and the base frequency voltage in conformance with load specifications or the
Base frequency.
Note:This is an important parameter that determines the constant torque control area.
Output voltage [V]
Base frequency voltage
XNX
XN
Output frequency (Hz)
0
Title Function Adjustment range Default setting
XN
Base frequency 1 25.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
XNX
Base frequency voltage1
50-330 (V) : 200V class
50-660 (V) : 400V class
230 (WP/WN type)
400 (WP type)
460 (WN type)