13.6 Siemens FLN
Currently, the XLTR-200 supports Siemens application number 2750. This
application acts as an FLN to Mitsubishi gateway.
13.6.1 Ports
For this application, the FLN network must be connected to XLTR-200
RS485 port A, and the Mitsubishi network must be connected to XLTR-200
RS485 port B.
The FLN port (RS485 port A) requires no configuration other than the FLN
node address, which has a valid address range of 0 – 98. NOTE
that the
factory default value is 99.
The baudrate and parity settings of the Mitsubishi port (RS485B port B)
must be configured to match the serial settings of the connected ASD.
NOTE
that the factory default values for these settings are 9600 baud, no
parity (8 data bits, 1 stop bit).
The ASD connected to RS485 port B must be configured as address #1 to
allow the gateway to communicate with it (parameter 117 or 331 = 1).
Refer to section 12.3.2 for information about using the serial console
interface to configure XLTR-200 ports.